English | Ελληνικά
Conventional Detectors & Fire Alarm Call Points

1 Description

  • Operation voltage 18-30V DC(smoke,heat)11-30V DC (gas)
  • Activation indication LED
  • BS-655.  The optical smoke sensor (or smoke particle detector) is activated when the obscuration rate caused by the smoke exceeds 3% per meter.
  • BS-657. Double technology sensor. It can be used to monitor an area of about  25-30 sqm.
  • BS-668. The heat detector is activated when the temperature of the monitored area exceeds 60 οC.  It can be used to monitor an area of about  50 sqm.
  • BS-685. Waterproof (IP 65) LPG detector with relay. It is activated when the gas content (propane or butane) in the monitored area exceeds 5-15% of the lower explosive level (L.E.L). The incorporated LED lights when the  detector is activated. The command towards that panel is given with a voltage free relay contact.
  • Activation relay(gas detectors)
  • Produced in accordance with European norms EΝ 54
  • BS-660. Heat of rise detector with base.
  • BS-661. Waterproof (IP 65),  heat of rise detector.
  • BS-686. Waterproof (IP 65) natural gas detector with relay. It is activated when the methane or alcohol content  in the monitored area exceeds 5-15% of the lower explosive level (L.E.L) The incorporated LED lights when the  detector is activated. The command towards that panel is given with a voltage free relay contact. 
  • Base-6024.This special base has an incorporated relay which is activated when the detector issues an alarm. It can be used to control devices (i.e. Sirens, Beacons) which must be activated in the event of an alarm condition.